UL 1424 FPL · FPLR Power Limited Fire Alarm Cable
– UL1424 소방 알람 케이블
  • R형 자동 화재 탐지설비의 신호용 배선 및 Network 통신배선용
  • 전기 · 전자기기의 신호용
  • 도체(Conductor) :

- TInned Copper Strands acc. to ASTM B33

- Base : IEC 60228 Class 5

- OEM : IEC 60228 Application

  • 절연체(Insulation) :

- UL Style No. 1015 & 10482 Specification Application

  • 테핑(Wrapping) :

- Aluminium Mylar Tape

  • 차폐층 (Screen)

- Tinned Copper braid Shield

내부시스(Covering)

- Optional

  • 테핑 :

- Aluminium Mylar tape

  • 시스체 (Sheath)

- UL Style no. 2643 Specification Application

  • 적용규격(Standard) :

- CM or CMR

  • 제품 정격(Style Rating) :

- 300V, 105°C

  • 스파크 절연 테스트(Spark Test Voltage)

- AC 4,000V (24AWG and smaill)

- AC 5,000V (23AWG and 20AWG)

- AC 6,000V (19AWG and 16AWG)

- AC 7,500V (14AWG and 2AWG)

  • 내전압 테스트(Dielectri Test Voltage)

- AC 2,000V (2AWG and smaller)

  • 난연성 테스트 (Fire Performance)

- Flame retardant and self-extinguishing

- VW-1 acc. to UL 1581 section 1080

- FT1 acc. to UL 1581 section 1060

  • Temp. Range

- Fixed Application : - 30°C ~ 70°C

- Flexible Application : No Specified

  • 특징 (Features) :

- Flexible and electrical character is excellent.

- Flammability excellent.

  • 제품허용공차 : ±5% 내외 (Tolerance : ±5%)
  • ODM 방식 및 상기표에 나타나 있지 않는 사항은 주문제작 방식으로 협의하여 UL 758 및 UL 1581에 적합하게 제작 가능
  • CE Marking 가능. (단, 본사와 협의 후 ODM 조건)

Cable Detail Data (케이블 세부 자료)

TypeAWG
Size
Pair
No.
Insulation Dia.
(mm)
Outer Dia.
(mm)
Approx. Weight
(kg/km)
Solid Type1811.805.1034.66
Solid Type1612.106.0051.15
Stranded Type1413.009.00100.31
Stranded Type1214.0011.50165.04