CONTINUOUS FLEX CABLE

KITRONIC DEVICENET

Fine Conductor / Foamed PE & PVC Insulation / Braid Shielded

INTRODUCE

DeviceNet is a bus system developed by Allen Bradley (Rockwell Automation). These cables are used to interconnect various industrial devices, such as SPS controls or limit switches. The special characteristic of this bus system is that a data pair and a power supply pair are integrated in one cable. These cables with PVC sheath are designed for fixed installation.

CONSTRUCTION
ConductorTinned annealed copper standard acc. to IEC 60228 EN 60228, VDE 0295 Class 6
Insulation18, 24AWG : Foamed Polyethylene compound
15, 22AWG : Special Poly Vinyl Chloride
Insulation Color18, 24AWG : White, Blue
15, 22AWG : Black, Red
FillerIf necessary
WrappingAluminium Mylar Foil Shield Tape
Drain WireTinned annealed copper standard acc. to IEC 60228 EN 60228, VDE 0295 Class 5
ShieldTinned copper wire Braid Shielded
SheathSpecial Poly Vinyl Chloride
Sheath ColorGray
OUTSTANDING FEATURES
  • Certified ODVA DeviceNet

  • Standard DeviceNet Cavle for data transmission

  • Variations prepared to match various use environment

  • Good EMC characteristics

  • No toxicity

  • No flame propagation

  • Flame retardant and self-extinguishing

TECHNICAL DATA
CertificationDeviceNet, UL
Nominal Rating80oC, 300V
Spark Test VoltageIAC 500V
Dielectric Test Voltage
Core/Core
AC 500V / 1 min
Core/ScreenAC 300V / 1 min
Conductor ResistanceThick18AWGMax. 22.60 Ω/km
15AWGMax. 11.80 Ω/km
Thin24AWGMax. 91.80 Ω/km
22AWGMax. 57.40 Ω/km
Insulation ResistanceThick18AWGMin. 10,000 MΩ/km
15AWGMin. 100 MΩ/km
Thin24AWGMin. 10,000 MΩ/km
22AWGMin. 100 MΩ/km
Mutual CapacitanceMax. 39.8 nF/m
Characteristics impedance120 ± 12 Ω
AttenuationThick125kHzMax. 0.42 dB/100m
500kHzMax. 0.81 dB/100m
Thin125kHzMax. 0.95 dB/100m
500kHzMax. 1.64 dB/100m
Toxicityacc. to RoHS
Fire performanceFlame retardant and self-extinguishing
acc. to IEC 60332-1, EN 60332-1
VW-1 acc. to UL 1581 section 1080
FT1 acc. to UL 1581 section 1060
0.2 CROSS SECTION DATA SHEET
No. of Cores
x cross section
(No. / ㎟)
Conductor
strands
(EA / ㎜)
Conductor
diameter
(㎜)
Insulation
diameter
(㎜)
Overall
diameter
(㎜)
Max.
current
(A)
2 x 0.240/0.080.581.053.94.0
3 x 0.240/0.080.581.054.23.5
4 x 0.240/0.080.581.054.52.8
6 x 0.240/0.080.581.055.22.5
8 x 0.240/0.080.581.055.92.3
10 x 0.240/0.080.581.056.62.2
12 x 0.240/0.080.581.056.52.1
15 x 0.240/0.080.581.057.02.1
20 x 0.240/0.080.581.057.81.9
0.3 CROSS SECTION DATA SHEET
No. of Cores
x cross section
(No. / ㎟)
Conductor
strands
(EA / ㎜)
Conductor
diameter
(㎜)
Insulation
diameter
(㎜)
Overall
diameter
(㎜)
Max.
current
(A)
2 x 0.360/0.080.721.254.44.8
3 x 0.360/0.080.721.254.64.2
4 x 0.360/0.080.721.255.13.4
6 x 0.360/0.080.721.255.82.9
8 x 0.360/0.080.721.256.72.7
10 x 0.360/0.080.721.257.52.6
12 x 0.360/0.080.721.257.42.5
15 x 0.360/0.080.721.257.92.5
20 x 0.360/0.080.721.259.02.3
0.5 CROSS SECTION DATA SHEET
No. of Cores
x cross section
(No. / ㎟)
Conductor
strands
(EA / ㎜)
Conductor
diameter
(㎜)
Insulation
diameter
(㎜)
Overall
diameter
(㎜)
Max.
current
(A)
2 x 0.57/14/0.081.041.655.36.4
3 x 0.57/14/0.081.041.655.65.6
4 x 0.57/14/0.081.041.656.14.5
6 x 0.57/14/0.081.041.657.23.9
8 x 0.57/14/0.081.041.658.33.6
10 x 0.57/14/0.081.041.659.43.4
12 x 0.57/14/0.081.041.659.33.4
15 x 0.57/14/0.081.041.6510.03.3
20 x 0.57/14/0.081.041.6511.53.0
0.75 CROSS SECTION DATA SHEET
No. of Cores
x cross section
(No. / ㎟)
Conductor
strands
(EA / ㎜)
Conductor
diameter
(㎜)
Insulation
diameter
(㎜)
Overall
diameter
(㎜)
Max.
current
(A)
2 x 0.757/20/0.081.242.006.18.8
3 x 0.757/20/0.081.242.006.57.7
4 x 0.757/20/0.081.242.007.16.2
6 x 0.757/20/0.081.242.008.35.4
8 x 0.757/20/0.081.242.009.75.0
10 x 0.757/20/0.081.242.0011.24.7
1.25 CROSS SECTION DATA SHEET
No. of Cores
x cross section
(No. / ㎟)
Conductor
strands
(EA / ㎜)
Conductor
diameter
(㎜)
Insulation
diameter
(㎜)
Overall
diameter
(㎜)
Max.
current
(A)
2 x 1.257/36/0.081.662.557.312.8
3 x 1.257/36/0.081.662.557.711.2
4 x 1.257/36/0.081.662.558.59.0
6 x 1.257/36/0.081.662.5510.27.8